Transfer station
The detailed transfer-station model: counter-flow heat exchanger with limited transfer capacity, secondary side from the heating curve, minimum modulation and heat deficit outputs
Overview
The transfer station (district sub station) is the detailed consumer model: a counter-flow heat exchanger with limited transfer capacity and a realistic representation of the secondary side (building heating). Unlike the simple heat exchanger, it can only deliver the required heat flux when the temperature conditions allow it – it is thus the correct model for undersupply scenarios, lowered network temperatures and networks with building-specific differing spreads.
How it works
Transfer capacity (UA value)
The transfer capacity of the station is determined from the design values:
The logarithmic temperature difference at the design point is the central quality parameter of the station: a smaller value means a larger, more efficient heat exchanger – the station manages with a smaller temperature gap between network and building and achieves lower network return temperatures. Typical values of modern stations are 5–10 K.
If the design temperatures of both sides are known, for the counter-flow heat exchanger can be computed directly. At the warm end the network supply faces the building supply, at the cold end the network return faces the building return:
Example: network 80/55 °C, building heating 70/50 °C yields and , hence . If both temperature differences are equal, then .
Secondary side from the heating curve
The secondary side (building heating) is determined from the heating curve of the building:
- Secondary supply setpoint = supply temperature of the heating curve at the current outdoor temperature
- Secondary spread = temperature difference of the heating curve (for a constant building demand: its constant spread)
- Secondary return:
- Secondary mass flux:
With these boundary conditions the model solves the counter-flow heat exchanger analytically and delivers the actually transferred heat flux as well as the outlet temperatures of both sides. The primary-side mass flux is adjusted by the consumer’s control so that the transferred heat flux matches the building demand – as far as the transfer capacity and the network supply temperature allow.
Minimum modulation
If the required heat flux falls below the minimum power , the station transfers no heat. This allows the cycling behavior of real stations with a modulation limit to be represented. The heat delivery that is thereby lost is made up via the storage term (see below).
Storage behavior
The model keeps an internal storage term , which sums the difference between delivered and required heat over time:
A negative value is a delivery backlog, a positive one a delivery surplus. The storage level corrects the target heat flux with which the station is operated:
A backlog thus increases the setpoint, a surplus lowers it – the accumulated energy difference is reduced again with a time constant of around 1000 s (≈ 17 minutes).
Physically, the storage term represents the thermal inertia of the building: short interruptions – cycling pauses due to the minimum modulation or briefly too-low supply temperatures – are not lost as energy, but are subsequently made up as soon as the conditions allow it. Over longer periods, the delivered energy sum thereby matches the demand profile; a cycling station with minimum modulation delivers the required power on average. The current storage level is available as the output quantity StoredHeatingEnergy. If the backlog can no longer be reduced because of an insufficient network supply temperature, this shows up in the heat deficit outputs.
Parameters
| Parameter | Unit | Default | Meaning |
|---|---|---|---|
| Nominal heating power | kW | 10 | Design power of the station; for the sized variant automatically = connection load of the building |
| Logarithmic temperature difference | K | 10 | Design value for the UA value determination |
| Minimum modulation | – | 0 | Minimum power as a fraction of the nominal power; below this no heat transfer |
| Nominal volume flow | m³/h | 2 | Reference volume flow for the pressure loss; sized variant: automatically from the connection load |
| Nominal pressure loss | bar | 0.5 | Pressure loss at the nominal volume flow (quadratic scaling) |
| Fluid volume | L | 3 | Fluid volume of the station |
Behavior under undersupply
If the network supply temperature drops, the driving temperature gradient in the heat exchanger drops – the station can then no longer fully cover the building demand, even with an increased primary-side mass flux. The transferred heat flux decreases for physical reasons, instead of being extracted unchanged as with the simple heat exchanger.
Persistent deficits are reported as output quantities:
| Quantity | Meaning |
|---|---|
| RequiredBuildingHeatFlux | Heat flux required by the building |
| HeatDeficitAbsolute | Non-deliverable heat flux [kW], as a time average, as soon as the delivery lies below 95 % of the requirement for longer than 30 minutes |
| HeatDeficitRelative | Deficit relative to the nominal heating power |
| OutletTemperatureSecondary / -Setpoint | Achieved vs. required secondary supply temperature |
| InletTemperatureSecondary | Secondary return temperature |
| StoredHeatingEnergy | Level of the internal storage term [kWh]: accumulated difference between delivered and required heat |
What you need to watch out for: heating curve and network supply temperature
The model stands or falls with a correctly set heating curve per building – it defines the secondary setpoint against which the heat exchanger works:
- The network supply temperature must lie above the secondary supply setpoint – and by at least the order of magnitude of the logarithmic design temperature difference. If, for example, the heating curve requires 70 °C at −12 °C outdoor temperature, but the network delivers only 72 °C, a station sized with cannot cover the demand: a permanent deficit arises that lies not in the network but in the parameterization.
- After the simulation, check the quantities HeatDeficitAbsolute and OutletTemperatureSecondary against the setpoint: systematic deviations already at mild outdoor temperatures indicate an unsuitable heating curve, deviations only on the coldest days indicate an actual capacity or temperature problem of the network.
- A too optimistically (small) chosen logarithmic temperature difference feigns a too-capable heat exchanger – use datasheet values of the planned stations where available.