Diversity and part load tab

Controls of the Diversity and part load tab: color mode, diversity and display settings, custom diversity per pipe and consumer settings.

VICUS Districts Page 2 of 3 in this chapter

Overview

The Diversity and part load tab in the network properties displays the diversity results as false colors in the network, controls the calculation and is used to edit the custom diversity of individual pipes as well as the part load ratio and diversity participation of individual consumers. The underlying calculation model is described on the page Diversity and Part Load.

Opening

The Network button in the toolbar of the 3D view opens the network properties; there, select the Diversity and part load tab. The tab is a single continuous page with five sections: color mode, diversity settings, display settings, custom diversity per pipe and consumer settings.

Color mode

The Color mode: selection field determines solely which quantity is displayed in color in the network - it does not show or hide any input fields.

EntryDisplay
Diversity resultsColors the pipes by their achieved diversity factor (continuous color scale, default). The legend is titled Achieved diversity or Effective diversity when the part load ratio is taken into account
Custom diversity per pipeColors only the pipes for which a custom diversity is set (legend Diversity factor)
Part load ratio per consumerColors the consumer nodes by their part load ratio (legend Part load ratio)
Diversity participation per consumerColors the consumer nodes by whether they participate in diversity (legend Diversity participation with the categories Participates in diversity (green) and Excluded from diversity (full peak) (orange); only the categories present in the network are listed)

Note: the color mode only determines the coloring. Whether the editing fields for the custom diversity or the consumer settings appear depends solely on the selection in the 3D view (pipe or consumer), not on the color mode - even though two entries have the same name.

Diversity settings

ElementMeaning
Consider diversityActivates diversity for the network. Only then do time shifts and reduced demands enter pipe sizing, steady-state calculation and dynamic simulation. Default: off
Recalculate diversityStarts the calculation directly with the most recently saved settings, without opening the settings dialog. If no settings have been saved yet, the defaults apply: maximum time shift 6 h, minimum load at peak 30 %, calculation accuracy Balanced, time step 20 min, minimum diversity 0.65. A progress bar shows the progress
Calculation settings…Opens the Diversity calculation dialog, in which settings and the target curve can be changed and the calculation can be run with a result display, see Diversity calculation

If the minimum load at the network peak cannot be reached for individual consumers within the maximum time shift, Recalculate diversity reports this with the warning Minimum load at network peak; the closest possible shift is used for these consumers.

Both buttons are only operable when Consider diversity is activated. A warning message appears as long as no valid results are available:

StateMessage
No resultsNo diversity results available. Click ‘Recalculate diversity’ to compute.
OutdatedDisplayed diversity results are outdated and may no longer match the current network.
InvalidStored diversity results are invalid and cannot be displayed. Recalculate to update the visualization.

Display settings

These two check boxes affect the display only. They are operable exclusively in the Diversity results color mode with diversity activated and valid results, otherwise grayed out. Default: both off.

ElementMeaning
Consider part load ratioMultiplies the displayed diversity values by the load-weighted part load ratio of each pipe; the legend changes from Achieved diversity to Effective diversity
Show time shifts of consumersLabels each consumer node with its optimized time shift, e.g. +2.00 h or -1.50 h. Positive values mean a delay, negative values an advance of the demand profile

Custom diversity per pipe

This section appears as soon as one or more pipes of the active network are selected (without a selection, it shows the hint Select a pipe to edit its custom diversity factor.).

ElementMeaning
Use custom diversityActivates a fixed target diversity factor for the selected pipes, which overrides the global target curve. Default: off
Diversity factor:Target diversity factor for the selected pipes, range 0.00 - 1.00, step 0.05. A value of 1.00 means no diversity (full peak load). Only operable when Use custom diversity is activated

The optimizer then tries to reach the specified factor for these pipes instead of the one derived from the curve. The value is used as entered - the Minimum diversity limit applies to the target curve only. This is useful when the default curve yields unrealistic values, for example on a main line with few, unusually large consumers.

In practice

The default curve assumes many similar consumers and reduces their peaks substantially. On a main line with only a few but very large consumers (e.g. industry or a large residential quarter on a single branch) this is often too optimistic. There, use Use custom diversity to deliberately set a higher, more conservative diversity factor - up to 1.00 for the full peak load. If, on the other hand, a single large consumer should always contribute its full peak, take it out of the optimization with Exclude from diversity (see below).

Consumer settings

This section appears as soon as one or more consumer nodes are selected (without a selection: Select a consumer to edit its part load ratio and diversity settings.). Only transfer stations are editable; junctions and source nodes are skipped.

ElementMeaning
Part load ratio:Fraction of the heating power that the consumer actually uses, range 0.00 - 1.00. A value of 1.00 corresponds to the full design load, smaller values reduce the applied heating power in the steady-state calculation and dynamic simulation. In pipe sizing it applies as soon as the dimensioning power is set to Actual maximum power - not with the connection power. A value of 0.00 removes the consumer from the load entirely; its service pipe is then given the smallest available pipe. Default: 1.00
Exclude from diversityThe selected consumers are not time-shifted by the diversity optimization and do not count for the target diversity of the pipes. Instead, their demand profile is shifted onto the peak load, so they always contribute their full peak (diversity factor 1), see concept. Suitable for large consumers such as commercial or industrial buildings. Default: off

Operating notes

  • Inputs are applied to all selected elements and can be undone.
  • With a multiple selection of differing values the field stays empty (or the check box shows an intermediate state); an entry then unifies all selected elements.
  • Without a selection both hints are shown at the same time; a mixed selection of pipe and consumer can show both editing sections.
  • Changing the part load ratio or the exclusion from diversity makes existing diversity results outdated.