Running pipe sizing
The Size pipes dialog: all options, the calculation workflow and manual rework of individual routes
VICUS Districts Page 2 of 6 in this chapter
Overview
The Size pipes dialog runs the automatic pipe sizing for the active network: it defines the fluid temperature, temperature difference, pipe selection and sizing criterion, and then assigns a pipe type to each route. After sizing, the fittings at the nodes are assigned automatically. The underlying calculation model is described in Calculation method.
Opening
- Menu Network › Size pipes …
- alternatively the
Size pipes … button in the Pipes tab of the network properties window
Prerequisite: the network must be fully connected, otherwise an error message appears and the dialog does not open.
Open ends (pipes that end at a junction without any further connection) are allowed for sizing: such a pipe carries no load itself and is sized with the smallest power of its adjacent pipes. When opened via the button in the Pipes tab, VICUS Districts first asks Open end found and offers Remove open end or Continue with open end. For the export to the simulation, however, open ends must be removed.

General tab
Network properties
| Option | Default | Unit | Meaning |
|---|---|---|---|
| Fluid temperature: | auto (empty) | °C | Nominal supply temperature to determine the temperature-dependent fluid viscosity. The field may be left empty (auto); the supply temperature is then determined from the plants or the heating curve of the network. |
| Temperature difference: | 4 | K | Nominal temperature difference between supply and return at the transfer stations; converts the consumer power into a mass flux. |
| Available pipes: | - | - | Number of the selected pipe types. The Select pipes … button opens a database dialog with a selection column: via the check boxes or the buttons to select and deselect you define which pipe types the algorithm may use. |
| Pipe fittings: | - | - | The Pipe fitting settings … button opens the settings dialog for the automatic fitting assignment, see Fittings. |
Sizing criteria
| Option | Default | Meaning |
|---|---|---|
| Dimensioning power: | Connection power (installed capacity) | Connection power (installed capacity) uses the installed connection power of each transfer station; part load ratios are not taken into account. Actual maximum power from the consumer demand (heating or cooling) uses the maximum of the actual consumer demand from the assigned demand profile. Heating and cooling are both considered; whichever imposes the larger load on the network is decisive. With a configured heat pump only the source-side share of the heating power loads the network (), while a cooling load is rejected into the network unchanged. The part load ratio entered for each consumer applies in addition. If no usable demand data is available for a consumer, it is sized with its connection power. In both cases the diversity factor is applied when diversity is activated; changing the dimensioning power makes existing diversity results outdated. |
| Sizing method: | Maximum pressure drop per pipe length | Criterion for the pipe selection per route: Maximum pressure drop per pipe length or Maximum pump pressure head (switches the input fields below). |
Method: Maximum pressure drop per pipe length
| Option | Default | Unit | Meaning |
|---|---|---|---|
| Maximum pipe pressure drop: | 150 | Pa/m | Maximum allowed pressure drop per pipe meter. For each route the smallest available pipe is chosen that stays below it. |
| Maximum velocity by DN: | disabled | - | Activates an additional velocity limit per nominal diameter. |
With the velocity limit activated, a table with the columns DN [mm] and Max velocity [m/s] appears; the velocity values are editable (multiple selection possible). A chart shows the table values as a solid curve (v_max) and the velocities calculated from the pressure-drop limit as a dashed reference curve (v(dp_max)).
Calculate velocities from maximum pressure drop recalculates the velocity limits from the currently set pressure-drop limit (iterative calculation with Colebrook friction coefficient and a roughness of 0.01 mm, see Calculation method). A query confirms overwriting the table.
Copy copies the table to the clipboard.
Method: Maximum pump pressure head
| Option | Default | Meaning |
|---|---|---|
| Supply type: | Central circulation pump | Central circulation pump: the table lists the energy plants (source nodes). Decentral circulation pumps: the table lists the transfer stations of the consumers. |
| Table Node name / Pump pressure head [bar] | - | Available head per pump in [bar], editable; with a multiple selection the entered value is applied to all selected rows. |
With this method the pipes are first pre-assigned according to the maximum pressure drop per pipe length and then corrected so that the total pressure loss along each supply path stays within the available pump head.
Energy center distribution assumptions tab
This tab is only active if the network contains at least one energy plant, and corresponds to the dialog under Network › Energy center distribution assumptions …, see Multiple energy plants.
Workflow and result
The Run sizing algorithm button starts the calculation; the progress is shown in a progress bar and can be stopped with Abort. Beforehand, the network topology and plant connections are checked: incorrectly connected nodes or wrongly wired plants - such as a plant wired inline into the pipe run that does not sit between exactly two pipes - abort with the message Invalid network and a list of the errors. If diversity is activated and no up-to-date results exist, the diversity optimization is run first. After completion:
- Each non-locked route has a pipe type assigned; afterwards the fittings at the nodes are reassigned automatically.
- If sizing was done with the actual maximum power and usable demand data is missing for individual consumers, the warning Incomplete demand data lists these consumers; they were sized with their connection power.
- Routes for which no pipe satisfies the criterion receive the largest available pipe and are listed in a warning message.
- With the maximum pump pressure head method a warning appears if the specified head is not sufficient.
- Locked pipes and nodes are skipped and listed in a notice message after a successful sizing.
The change is transferred into the project as an undo step. If Close dialog when finished is activated (default), the dialog closes automatically after a successful completion.
Manual rework
Individual routes can be reworked in the Pipes tab of the network properties window:
- The table in the Pipe properties display mode lists all pipe types used in the network with color, manufacturer, product and name.
Edit… opens the selected pipe type in the pipe database.
Exchange… replaces the selected pipe type throughout the network with another one.
Select selects all routes with this pipe type in the 3D scene.
For individual routes selected in the scene, Assign from DB… and Assign from Table directly assign a different pipe type. When editing locked routes a safety query is issued.
By the way
A manual pipe swap changes the diameters at the nodes and thus the reducers and T-pieces. VICUS Districts reassigns the fittings of the affected nodes automatically when assigning and exchanging pipes; you only need Recalculate pipe fittings … if you want to change the pipe fitting settings. With Exchange… you replace a pipe type network-wide in a single step, which saves a lot of manual work when product ranges are swapped afterwards.
