Worst-point control

District heating network, part 7: configure worst-point control for optimal pump regulation

Overview

This part demonstrates how to install a more efficient pump control. In the previous parts, a pump with a constant pressure increase was used. Here, a controlled pump is used instead, which regulates on a worst point.

Installing a controlled pump

Replacing the constant pump with a controlled pump in the plant editor
Replacement: remove the constant-head pump and insert a controlled pump
  1. Open the energy plant and remove the current pump (with constant head, delta-p-c).
  2. Insert a pump with controlled head and reconnect it.

Controller settings

Worst-point control with 0.6 bar pressure difference and selection of all network points
Controller settings: worst-point control on 0.6 bar pressure difference with all network points

In the settings of the controlled pump:

  1. Select worst-point control as the controller.
  2. Set the pressure difference that is to be maintained at the worst point slightly higher than the maximum pressure loss of the transfer stations. With a maximum transfer-station pressure loss of 0.5 bar, 0.6 bar is chosen, for example, to always guarantee a positive pressure difference across every transfer station.
  3. Under Worst point, select the points to be considered. In the simplest case: all points in the network — the simulation then automatically determines the point with the lowest pressure difference at every time step.

Important: A worst point must always be selected, otherwise the system is flagged as invalid.

Steady-state calculation and pump sizing

  1. Calculate the network in steady state — the pressure loss (e.g. 1.6 bar at a 15 Kelvin spread) has not changed.
  2. Under Results > Pump sizing, re-size the pump. Since a controlled pump is now installed, a matching manufacturer data set must be assigned.
  3. Select a suitable pump from the list and assign it.

Setting the worst point from steady-state results

Targeted selection of the worst point from the steady-state results
Alternative: set a specific worst point from the steady-state calculation results

As an alternative to the automatic worst point, a specific worst point can also be set from the steady-state results.

Simulation and results

After starting the simulation (e.g. over 14 days), the results show:

Checking the temperature difference

With the simple transfer stations, it is important to check the temperature difference. The desired 15 Kelvin is largely maintained — small overshoots are attributable to the somewhat slower pump control and are usually uncritical.

Pump diagram

Pump diagram with quadratic curve due to worst-point control
Pump diagram: quadratic curve due to worst-point control instead of constant pressure increase

The pump diagram shows the difference from constant pressure increase: with worst-point control, the head settles along a quadratic curve. The control follows the system curve, which brings significantly higher efficiency and, above all, a lower electricity demand of the pump.

Head profile

Head profile: variable head instead of constant 1.6 bar
Variable head: the pump adapts to demand — lower electricity demand compared to constant head

The head profile makes the difference clear: instead of a constant 1.6 bar, the pump moves with the network demand and settles lower when less heat is needed. In the evaluation, this shows up as a lower electricity demand.

By the way:

The savings effect is considerable because the electrical pump power along the system curve falls with the third power of the speed: even a moderate reduction of the head at part load lowers the electricity consumption disproportionately. Since a heat network runs in part load for most of the year, the controlled pump usually pays for itself quickly compared to the constant-delivery pump — while the worst point always remains adequately supplied.

Video tutorial

Stay up to date

New features, tutorials and updates delivered to your inbox.