Heat pumps

Heat pump model with a biquadratic COP polynomial: source-side for cold district heating, supply-side as central generator, with power and limits.

VICUS Districts Page 12 of 14 in this chapter

Overview

The heat pump model computes the coefficient of performance (COP) and the electrical power via a biquadratic polynomial from evaporator and condenser temperature. There are two integration variants:

  • source side (heat pump source side) – a consumer model: the heat pump sits at the building, its evaporator is part of the network. It extracts heat from the network and raises it to the temperature level of the building heating. Typical applications: consumers in cold district heating (5GDHC) as well as booster heat pumps in low-temperature networks whose supply temperature is not sufficient for heating or domestic hot water of individual buildings.
  • supply side (heat pump supply side) – a model for the energy plant: the heat pump feeds into the network as a central generator, its condenser is part of the network. It obtains the source heat from outside (e.g. geothermal energy, waste heat).

Good to know

Mnemonic for the integration: source side = the heat pump stands at the building and extracts heat from the network via its evaporator (cold district heating, booster). Supply side = the heat pump feeds into the network as a central generator via its condenser. Same COP physics, opposite role in the network.

COP calculation

The COP is computed from the evaporator temperature TET_E and the condenser temperature TCT_C, each in Kelvin. On the network side the mean fluid temperature (mean of inlet and outlet temperature) is used; the other side is prescribed:

  • source side: TET_E = mean fluid temperature; TCT_C = supply temperature of the building’s heating curve (with constant demand: the constant heating setpoint)
  • supply side: TCT_C = mean fluid temperature; TET_E = prescribed source temperature (Heat exchange tab)

COP=c0+c1TE+c2TC+c3TETC+c4TE2+c5TC2COP = c_0 + c_1 T_E + c_2 T_C + c_3 T_E T_C + c_4 T_E^2 + c_5 T_C^2

The coefficients of the COP polynomial are stored in the component; the component editor shows the COP characteristic as a diagram but offers no input fields for the coefficients. The default coefficients describe a typical brine/water heat pump (e.g. COP ≈ 5.8 at a 10 °C source and a 35 °C sink temperature).

Operating limits of the model:

  • The COP is limited to a maximum of 15: small or even negative temperature lifts yield COP = 15, and the heat pump keeps running (continuous, numerically robust behavior).
  • If the polynomial yields a COP ≤ 1 (invalid operating point of the polynomial), the heat pump switches off – no heat is transferred.

Electrical power and evaporator power follow from the energy balance:

Pel=Q˙condCOPQ˙evap=Q˙cond⋅COP−1COPP_{el} = \frac{\dot Q_{cond}}{COP} \qquad\qquad \dot Q_{evap} = \dot Q_{cond} \cdot \frac{COP - 1}{COP}

Heat pump, source side (consumer)

This variant is used in consumer plants – in cold district heating as a regular transfer to the building or as a booster heat pump. The condenser power is the current heating demand of the building, limited by the maximum heating power. The condenser temperature is the supply temperature of the heating curve of the building (temperature level of the heating system; with constant demand the constant heating setpoint). The evaporator power Q˙evap\dot Q_{evap} is extracted from the network – that is, the building demand minus the electrical share.

For a negative building demand (cooling case) the model works as passive cooling: the heat pump is off, and the cooling load is fed to the network directly as heat – the usual summer behavior in cold district heating networks. Passive cooling is not limited by the maximum heating power.

ParameterUnitDefaultMeaning
Maximum heating powerkW–Upper limit of the condenser power; for the sized variant automatically = maximum heating demand of the building (not COP-corrected)
COP polynomial–default coefficientsCoefficients c0…c5c_0 \dots c_5; only shown as a diagram in the editor
Nominal volume flowm³/h2Reference volume flow for the pressure loss; sized variant: automatically from the connection power
Nominal pressure lossbar0.5 (sized: 0.2)Pressure loss at the nominal volume flow (quadratic scaling)
Parameters of the source-side heat pump with nominal pressure loss and the COP polynomial as a curve
Parameters of the source-side heat pump: the COP is described by a polynomial (COP curve) depending on the temperatures.

Heat pump, supply side (central generator)

This variant is used in the plant of the energy plant. As a central generator, the heat pump heats the network to the supply setpoint of the heating curve assigned to the component in the component editor:

Q˙cond=m˙ cp (TSF,target−Tin)\dot Q_{cond} = \dot m \, c_p \, (T_{SF,target} - T_{in})

limited by the maximum heating power. The heat pump only heats: for a negative heat demand or reverse flow it delivers no power. The evaporator temperature (heat source) must be prescribed as a boundary condition – constant or as a time series via the Heat exchange tab. A heating curve is required.

ParameterUnitDefaultMeaning
Maximum heating powerkW–Upper limit of the condenser power
COP polynomial–default coefficientsCoefficients c0…c5c_0 \dots c_5; only shown as a diagram in the editor
Nominal volume flowm³/h2Reference volume flow for the pressure loss
Nominal pressure lossbar0.5Pressure loss at the nominal volume flow

Auto size … determines the maximum heating power and the nominal volume flow rate from the network: the Auto-sizing dialog sums the maximum heating power of all consumers of the active network, adds the Network losses: (in %) and multiplies by the Coverage: (in %) of the generator. The nominal volume flow rate follows from this power and the temperature difference of the network. Apply to component takes over both values.

Output quantities

QuantityMeaning
COPCurrent coefficient of performance
ElectricalPowerElectrical power consumption
CondenserHeatFluxCondenser power (heating power)
EvaporatorHeatFluxEvaporator power (source heat)
EvaporatorMeanTemperature / CondenserMeanTemperatureTemperatures used for the COP calculation (not part of the default outputs)
FlowElementHeatLossHeat flux exchanged with the fluid on the network side (positive = extracted from the network; source side: equal to the evaporator heat flux)
TemperatureDifferenceInlet minus outlet temperature on the network side; 0 when the heat pump is idle

From ElectricalPower, seasonal performance factors and electricity costs can be evaluated – see Line charts.

Notes

  • Cold district heating: the COP correction is done at the consumer node. If a heat pump with a Nominal COP is set there, the connection power results as Pconn=Pheat⋅(1−1/COP)P_{conn} = P_{heat} \cdot (1 - 1/COP) – i.e. the evaporator power extracted from the network. The automatic sizing derives the nominal volume flow from it. The maximum heating power, by contrast, is not COP-corrected (condenser side = peak demand of the building).
  • If the network temperature drops sharply in winter, the COP of the source-side heat pumps drops – the electrical power rises. A look at the COP time series of the critical consumers is part of the evaluation of cold networks.
  • The fluid volume of the heat pumps cannot be changed in the user interface (default 10 L), see Component reference.

Stay up to date

New features, tutorials and updates delivered to your inbox.