Heat pumps
Heat pump model with a biquadratic COP polynomial: source-side for cold district heating, supply-side as central generator, with power and limits.
VICUS Districts Page 12 of 14 in this chapter
Overview
The heat pump model computes the coefficient of performance (COP) and the electrical power via a biquadratic polynomial from evaporator and condenser temperature. There are two integration variants:
- source side (heat pump source side) – a consumer model: the heat pump sits at the building, its evaporator is part of the network. It extracts heat from the network and raises it to the temperature level of the building heating. Typical applications: consumers in cold district heating (5GDHC) as well as booster heat pumps in low-temperature networks whose supply temperature is not sufficient for heating or domestic hot water of individual buildings.
- supply side (heat pump supply side) – a model for the energy plant: the heat pump feeds into the network as a central generator, its condenser is part of the network. It obtains the source heat from outside (e.g. geothermal energy, waste heat).
Good to know
Mnemonic for the integration: source side = the heat pump stands at the building and extracts heat from the network via its evaporator (cold district heating, booster). Supply side = the heat pump feeds into the network as a central generator via its condenser. Same COP physics, opposite role in the network.
COP calculation
The COP is computed from the evaporator temperature and the condenser temperature , each in Kelvin. On the network side the mean fluid temperature (mean of inlet and outlet temperature) is used; the other side is prescribed:
- source side: = mean fluid temperature; = supply temperature of the building’s heating curve (with constant demand: the constant heating setpoint)
- supply side: = mean fluid temperature; = prescribed source temperature (Heat exchange tab)
The coefficients of the COP polynomial are stored in the component; the component editor shows the COP characteristic as a diagram but offers no input fields for the coefficients. The default coefficients describe a typical brine/water heat pump (e.g. COP ≈ 5.8 at a 10 °C source and a 35 °C sink temperature).
Operating limits of the model:
- The COP is limited to a maximum of 15: small or even negative temperature lifts yield COP = 15, and the heat pump keeps running (continuous, numerically robust behavior).
- If the polynomial yields a COP ≤ 1 (invalid operating point of the polynomial), the heat pump switches off – no heat is transferred.
Electrical power and evaporator power follow from the energy balance:
Heat pump, source side (consumer)
This variant is used in consumer plants – in cold district heating as a regular transfer to the building or as a booster heat pump. The condenser power is the current heating demand of the building, limited by the maximum heating power. The condenser temperature is the supply temperature of the heating curve of the building (temperature level of the heating system; with constant demand the constant heating setpoint). The evaporator power is extracted from the network – that is, the building demand minus the electrical share.
For a negative building demand (cooling case) the model works as passive cooling: the heat pump is off, and the cooling load is fed to the network directly as heat – the usual summer behavior in cold district heating networks. Passive cooling is not limited by the maximum heating power.
| Parameter | Unit | Default | Meaning |
|---|---|---|---|
| Maximum heating power | kW | – | Upper limit of the condenser power; for the sized variant automatically = maximum heating demand of the building (not COP-corrected) |
| COP polynomial | – | default coefficients | Coefficients ; only shown as a diagram in the editor |
| Nominal volume flow | m³/h | 2 | Reference volume flow for the pressure loss; sized variant: automatically from the connection power |
| Nominal pressure loss | bar | 0.5 (sized: 0.2) | Pressure loss at the nominal volume flow (quadratic scaling) |
Heat pump, supply side (central generator)
This variant is used in the plant of the energy plant. As a central generator, the heat pump heats the network to the supply setpoint of the heating curve assigned to the component in the component editor:
limited by the maximum heating power. The heat pump only heats: for a negative heat demand or reverse flow it delivers no power. The evaporator temperature (heat source) must be prescribed as a boundary condition – constant or as a time series via the Heat exchange tab. A heating curve is required.
| Parameter | Unit | Default | Meaning |
|---|---|---|---|
| Maximum heating power | kW | – | Upper limit of the condenser power |
| COP polynomial | – | default coefficients | Coefficients ; only shown as a diagram in the editor |
| Nominal volume flow | m³/h | 2 | Reference volume flow for the pressure loss |
| Nominal pressure loss | bar | 0.5 | Pressure loss at the nominal volume flow |
Auto size … determines the maximum heating power and the nominal volume flow rate from the network: the Auto-sizing dialog sums the maximum heating power of all consumers of the active network, adds the Network losses: (in %) and multiplies by the Coverage: (in %) of the generator. The nominal volume flow rate follows from this power and the temperature difference of the network. Apply to component takes over both values.
Output quantities
| Quantity | Meaning |
|---|---|
| COP | Current coefficient of performance |
| ElectricalPower | Electrical power consumption |
| CondenserHeatFlux | Condenser power (heating power) |
| EvaporatorHeatFlux | Evaporator power (source heat) |
| EvaporatorMeanTemperature / CondenserMeanTemperature | Temperatures used for the COP calculation (not part of the default outputs) |
| FlowElementHeatLoss | Heat flux exchanged with the fluid on the network side (positive = extracted from the network; source side: equal to the evaporator heat flux) |
| TemperatureDifference | Inlet minus outlet temperature on the network side; 0 when the heat pump is idle |
From ElectricalPower, seasonal performance factors and electricity costs can be evaluated – see Line charts.
Notes
- Cold district heating: the COP correction is done at the consumer node. If a heat pump with a Nominal COP is set there, the connection power results as – i.e. the evaporator power extracted from the network. The automatic sizing derives the nominal volume flow from it. The maximum heating power, by contrast, is not COP-corrected (condenser side = peak demand of the building).
- If the network temperature drops sharply in winter, the COP of the source-side heat pumps drops – the electrical power rises. A look at the COP time series of the critical consumers is part of the evaluation of cold networks.
- The fluid volume of the heat pumps cannot be changed in the user interface (default 10 L), see Component reference.