Pressure losses & valves

Pressure loss and valve components: controlled valve with Kvs value, constant and quadratic pressure loss elements, zeta element, non-return valve, building internal installation

Overview

These components represent pressure losses and valves. They are hydraulically relevant but – with the exception of the fluid volume – exchange no heat with the surroundings.

Controlled valve

The controlled valve throttles the flow according to the assigned controller. It is the standard valve for flow-rate control at the consumer. Controllable quantities are:

  • Mass flux – setpoint mass flux through the branch
  • Temperature difference of the following element – e.g. a constant spread across the consumer’s heat exchanger
  • Outlet temperature on the secondary side – control to the secondary-side outlet temperature of a transfer station
ParameterUnitDefaultMeaning
Kvs valuem³/hoptionalFlow coefficient: volume flow at 1 bar pressure loss in the fully open state
Fluid volumeL0.5Fluid volume of the valve

If a Kvs value is set, the base pressure loss of the open valve results as

Δp0=1bar(V˙Kvs)2\Delta p_0 = 1\,\text{bar} \cdot \left( \frac{\dot V}{K_{vs}} \right)^2

The controller increases the pressure loss beyond this in order to meet the setpoint. Without a Kvs value the valve acts purely as an actuator with no base pressure loss.

Good to know:

A set Kvs value makes the controlled valve more realistic: it then already has a base pressure loss in the open state, which the controller only increases further. For pure sizing the ideal actuator without a Kvs value is sufficient; for reliable pressure losses at the consumer, enter the Kvs value from the valve datasheet.

Element, constant pressure loss

An element with a fixed pressure loss independent of the volume flow – for example for a differential pressure controller or a lump-sum built-in component.

ParameterUnitDefaultMeaning
Pressure lossbar0.2Constant pressure loss (sign follows the flow direction)
Fluid volumeL0.5Fluid volume

Element, quadratic pressure loss

The pressure loss scales quadratically with the volume flow, defined via a nominal point – the usual model for apparatus whose design pressure loss is known from the datasheet:

Δp=Δpnom(V˙V˙nom)2\Delta p = \Delta p_{nom} \cdot \left( \frac{\dot V}{\dot V_{nom}} \right)^2

ParameterUnitDefaultMeaning
Nominal pressure lossbar0.2Pressure loss at the nominal volume flow
Nominal volume flowm³/h10Reference volume flow
Fluid volumeL1Fluid volume

Element, defined zeta

The pressure loss is computed from a resistance coefficient (zeta value) and the flow velocity – suitable for fittings and built-in components with tabulated zeta values:

Δp=ζρ2vvwithv=m˙ρA(dhyd)\Delta p = \zeta \cdot \frac{\rho}{2} \, v \, |v| \qquad \text{with} \qquad v = \frac{\dot m}{\rho \cdot A(d_{hyd})}

ParameterUnitDefaultMeaning
Pressure loss coefficient (zeta value)150Resistance coefficient of the element
Hydraulic diametermm50Reference diameter for the flow velocity
Fluid volumeL1Fluid volume

Non-return valve

The non-return valve prevents reverse flow: in the blocking direction the model applies a very high pressure loss, in the flow direction it is resistance-free. The transition is numerically smoothed so that the equation solver remains stable. The valve has no parameters.

Typical application: parallel generators or branches that must not be flowed through in reverse.

Building internal installation

This component represents the pressure loss of the pipe installation in the building – from the house connection to the transfer station – without the lines having to be drawn individually. The pressure loss is computed from the specified pipe length and the configured fittings (e.g. bends); the pipe dimension is automatically taken from the adjacent connection pipe of the network.

ParameterUnitDefaultMeaning
Pipe lengthm20Single line length in the building; it is internally doubled for supply and return
FittingsNumber and type of fittings (e.g. bends); the zeta values are summed and likewise applied for supply and return

The pipe length and fittings of the building internal installation can optionally be counted in the bill of materials.

Notes

  • A controller is required only by the controlled valve; all other elements on this page are passive.
  • None of these elements support a heat exchange type – they are adiabatic.

Stay up to date

New features, tutorials and updates delivered to your inbox.