Pressure losses & valves

Pressure losses and valves: controlled valve, thermostatic bypass, elements with constant, quadratic, Kvs or zeta pressure loss, non-return valve.

Overview

These components represent pressure losses and valves. They are hydraulically relevant but – with the exception of the fluid volume – exchange no heat with the surroundings.

Controlled valve

The controlled valve throttles the flow according to the assigned controller. It is the standard valve for flow-rate control at the consumer. Controllable quantities are:

  • Mass flux – setpoint mass flux through the branch
  • Temperature difference of the following element – e.g. a constant spread across the consumer’s heat exchanger
  • Outlet temperature on the secondary side – control to the secondary-side outlet temperature of a transfer station
  • Minimum inlet temperature (thermostatic bypass) – the valve acts as a thermostatic bypass, see below
ParameterUnitDefaultMeaning
Flow factor Kvsm³/hoptionalVolume flow at 1 bar pressure loss in the fully open state; required for the thermostatic bypass

If a Kvs value is set, the base pressure loss of the open valve results as

Δp0=1 bar⋅(V˙Kvs)2\Delta p_0 = 1\,\text{bar} \cdot \left( \frac{\dot V}{K_{vs}} \right)^2

The controller increases the pressure loss beyond this in order to meet the setpoint. Without a Kvs value the valve acts purely as an actuator with no base pressure loss.

Good to know

A set Kvs value makes the controlled valve more realistic: it then already has a base pressure loss in the open state, which the controller only increases further. For pure sizing the ideal actuator without a Kvs value is sufficient; for reliable pressure losses at the consumer, enter the Kvs value from the valve datasheet.

Parameters of the controlled valve with flow factor Kvs and assigned controller
Parameters of the controlled valve: the flow factor Kvs and the assigned controller determine the pressure loss.

Thermostatic bypass

With the controlled property Minimum inlet temperature (thermostatic bypass) the controlled valve becomes a thermostatic bypass. Connected in parallel to the substation or heat exchanger of a consumer, it keeps the connection pipe warm at low demand (e.g. in summer): when the temperature at the valve inlet drops below the set point, the valve opens and lets supply water flow directly into the return.

The opening follows a P controller: it grows by Kp per kelvin below the set point and is complete 1/Kp1/K_p below the set point. The effective flow factor is Kv=Kvs⋅openingK_v = K_{vs} \cdot \text{opening}; the pressure loss follows from it as for the open valve. A closed bypass keeps a residual opening of 1 % of the Kvs value so that the temperature sensor notices the connection pipe cooling down. The inlet temperature is evaluated every 10 minutes; in between, the opening is held constant.

SettingDefaultMeaning
Flow factor Kvs–Kvs of the fully open bypass; without Kvs the component is invalid
Temperature set point50 °CInlet temperature below which the bypass opens; alternatively as a schedule
Kp0.25 1/KOpening per kelvin below the set point; with 0.25 1/K the bypass is fully open at 46 °C

Only the P controller is available as controller type, see Controllers. The built-in plant Substation with bypass contains such a bypass ready-wired (Kvs = 0.1 m³/h); for the simplified consumer it can be added with the option Thermostatic bypass, see Plant concept.

Element, constant pressure loss

An element with a fixed pressure loss independent of the volume flow – for example for a differential pressure controller or a lump-sum built-in component.

ParameterUnitDefaultMeaning
Pressure loss of valvebar0.2Constant pressure loss (sign follows the flow direction)

Element, quadratic pressure loss

The pressure loss scales quadratically with the volume flow, defined via a nominal point – the usual model for apparatus whose design pressure loss is known from the datasheet:

Δp=Δpnom⋅(V˙V˙nom)2\Delta p = \Delta p_{nom} \cdot \left( \frac{\dot V}{\dot V_{nom}} \right)^2

ParameterUnitDefaultMeaning
Nominal pressure lossbar0.2Pressure loss at the nominal volume flow
Nominal volume flow ratem³/h10Reference volume flow

Element, defined Kvs

A passive element with a fixed Kvs value – for example a balancing valve, a strainer or a heat meter for which the datasheet states a Kvs value. The pressure loss rises quadratically with the volume flow; at V˙=Kvs\dot V = K_{vs} it is exactly 1 bar:

Δp=1 bar⋅(V˙Kvs)2\Delta p = 1\,\text{bar} \cdot \left( \frac{\dot V}{K_{vs}} \right)^2

ParameterUnitDefaultMeaning
Flow factor Kvsm³/h10Volume flow at 1 bar pressure loss

Compared with the quadratic pressure loss element, no conversion to a nominal point is needed: the Kvs value from the datasheet is entered directly. The pressure loss is available as the output quantity PressureLossBase.

Element, defined zeta

The pressure loss is computed from a resistance coefficient (zeta value) and the flow velocity – suitable for fittings and built-in components with tabulated zeta values:

Δp=ζ⋅ρ2 v ∣v∣withv=m˙ρ⋅A(dhyd)\Delta p = \zeta \cdot \frac{\rho}{2} \, v \, |v| \qquad \text{with} \qquad v = \frac{\dot m}{\rho \cdot A(d_{hyd})}

ParameterUnitDefaultMeaning
Pressure loss coefficient (zeta-value)–150Resistance coefficient of the element
Hydraulic diametermm50Reference diameter for the flow velocity

Non-return valve

The non-return valve prevents reverse flow: backflow is blocked by a steeply increasing pressure difference, which as a smooth function remains numerically stable. At normal flow rates in the flow direction the valve has practically no pressure loss. The valve has no parameters.

Typical application: parallel generators or branches that must not be flowed through in reverse.

Building internal installation

This component represents the pressure loss of the pipe installation in the building – from the house connection to the transfer station – without the lines having to be drawn individually. The pressure loss is computed from the specified pipe length and the configured fittings (e.g. bends); the pipe dimension is automatically taken from the adjacent connection pipe of the network.

ParameterUnitDefaultMeaning
Pipe lengthm20Single line length in the building; it is internally doubled for supply and return
Fittings––Number and type of fittings (e.g. bends); the zeta values are summed and likewise applied for supply and return

The pipe length and fittings of the building internal installation are always included in the bill of materials.

Notes

  • A controller is required only by the controlled valve; all other elements on this page are passive.
  • None of these elements support a heat exchange type – they are adiabatic.
  • The fluid volume of the elements cannot be changed in the user interface (default 10 L), see Component reference.

Stay up to date

New features, tutorials and updates delivered to your inbox.