Pressure losses & valves
Pressure losses and valves: controlled valve, thermostatic bypass, elements with constant, quadratic, Kvs or zeta pressure loss, non-return valve.
Overview
These components represent pressure losses and valves. They are hydraulically relevant but – with the exception of the fluid volume – exchange no heat with the surroundings.
Controlled valve
The controlled valve throttles the flow according to the assigned controller. It is the standard valve for flow-rate control at the consumer. Controllable quantities are:
- Mass flux – setpoint mass flux through the branch
- Temperature difference of the following element – e.g. a constant spread across the consumer’s heat exchanger
- Outlet temperature on the secondary side – control to the secondary-side outlet temperature of a transfer station
- Minimum inlet temperature (thermostatic bypass) – the valve acts as a thermostatic bypass, see below
| Parameter | Unit | Default | Meaning |
|---|---|---|---|
| Flow factor Kvs | m³/h | optional | Volume flow at 1 bar pressure loss in the fully open state; required for the thermostatic bypass |
If a Kvs value is set, the base pressure loss of the open valve results as
The controller increases the pressure loss beyond this in order to meet the setpoint. Without a Kvs value the valve acts purely as an actuator with no base pressure loss.
Good to know
A set Kvs value makes the controlled valve more realistic: it then already has a base pressure loss in the open state, which the controller only increases further. For pure sizing the ideal actuator without a Kvs value is sufficient; for reliable pressure losses at the consumer, enter the Kvs value from the valve datasheet.
Thermostatic bypass
With the controlled property Minimum inlet temperature (thermostatic bypass) the controlled valve becomes a thermostatic bypass. Connected in parallel to the substation or heat exchanger of a consumer, it keeps the connection pipe warm at low demand (e.g. in summer): when the temperature at the valve inlet drops below the set point, the valve opens and lets supply water flow directly into the return.
The opening follows a P controller: it grows by Kp per kelvin below the set point and is complete below the set point. The effective flow factor is ; the pressure loss follows from it as for the open valve. A closed bypass keeps a residual opening of 1 % of the Kvs value so that the temperature sensor notices the connection pipe cooling down. The inlet temperature is evaluated every 10 minutes; in between, the opening is held constant.
| Setting | Default | Meaning |
|---|---|---|
| Flow factor Kvs | – | Kvs of the fully open bypass; without Kvs the component is invalid |
| Temperature set point | 50 °C | Inlet temperature below which the bypass opens; alternatively as a schedule |
| Kp | 0.25 1/K | Opening per kelvin below the set point; with 0.25 1/K the bypass is fully open at 46 °C |
Only the P controller is available as controller type, see Controllers. The built-in plant Substation with bypass contains such a bypass ready-wired (Kvs = 0.1 m³/h); for the simplified consumer it can be added with the option Thermostatic bypass, see Plant concept.
Element, constant pressure loss
An element with a fixed pressure loss independent of the volume flow – for example for a differential pressure controller or a lump-sum built-in component.
| Parameter | Unit | Default | Meaning |
|---|---|---|---|
| Pressure loss of valve | bar | 0.2 | Constant pressure loss (sign follows the flow direction) |
Element, quadratic pressure loss
The pressure loss scales quadratically with the volume flow, defined via a nominal point – the usual model for apparatus whose design pressure loss is known from the datasheet:
| Parameter | Unit | Default | Meaning |
|---|---|---|---|
| Nominal pressure loss | bar | 0.2 | Pressure loss at the nominal volume flow |
| Nominal volume flow rate | m³/h | 10 | Reference volume flow |
Element, defined Kvs
A passive element with a fixed Kvs value – for example a balancing valve, a strainer or a heat meter for which the datasheet states a Kvs value. The pressure loss rises quadratically with the volume flow; at it is exactly 1 bar:
| Parameter | Unit | Default | Meaning |
|---|---|---|---|
| Flow factor Kvs | m³/h | 10 | Volume flow at 1 bar pressure loss |
Compared with the quadratic pressure loss element, no conversion to a nominal point is needed: the Kvs value from the datasheet is entered directly. The pressure loss is available as the output quantity PressureLossBase.
Element, defined zeta
The pressure loss is computed from a resistance coefficient (zeta value) and the flow velocity – suitable for fittings and built-in components with tabulated zeta values:
| Parameter | Unit | Default | Meaning |
|---|---|---|---|
| Pressure loss coefficient (zeta-value) | – | 150 | Resistance coefficient of the element |
| Hydraulic diameter | mm | 50 | Reference diameter for the flow velocity |
Non-return valve
The non-return valve prevents reverse flow: backflow is blocked by a steeply increasing pressure difference, which as a smooth function remains numerically stable. At normal flow rates in the flow direction the valve has practically no pressure loss. The valve has no parameters.
Typical application: parallel generators or branches that must not be flowed through in reverse.
Building internal installation
This component represents the pressure loss of the pipe installation in the building – from the house connection to the transfer station – without the lines having to be drawn individually. The pressure loss is computed from the specified pipe length and the configured fittings (e.g. bends); the pipe dimension is automatically taken from the adjacent connection pipe of the network.
| Parameter | Unit | Default | Meaning |
|---|---|---|---|
| Pipe length | m | 20 | Single line length in the building; it is internally doubled for supply and return |
| Fittings | – | – | Number and type of fittings (e.g. bends); the zeta values are summed and likewise applied for supply and return |
The pipe length and fittings of the building internal installation are always included in the bill of materials.
Notes
- A controller is required only by the controlled valve; all other elements on this page are passive.
- None of these elements support a heat exchange type – they are adiabatic.
- The fluid volume of the elements cannot be changed in the user interface (default 10 L), see Component reference.